The plant itself: building design and repair, air handling, pressure differentials, temperature and humidity. FDAgent finds 160 such observations in 121 Form 483s issued to 117 facilities, for inspections that ended between October 2008 and September 2026. Each is quoted below from the 483 FDA posted.

A Form 483 lists the investigators' observations at the end of an inspection. It is not FDA's final determination.

Source: Form 483 PDFs in FDA's Electronic Reading Room, last synced Nov 23, 2026, 04:33 UTC. Every quote is from a 483 whose reading passed FDAgent's checks against the scan. FDAgent is independent of FDA.

Observations
160
Each quoted below
Form 483s
121
Posted by FDA
Facilities
117
Distinct FEIs
Most recent
Sep 10, 2026
Inspection end date

Observations by year

These observations by the year the inspection ended. They follow which 483s FDA has posted and FDAgent has read, so they show what is on record, not a trend in FDA's findings. 2026 runs to the latest sync (lighter bar).

Peak: 49 in 2026

Facilities and HVAC observations in Form 483s by inspection year
YearObservations
20081
20091
20100
20110
20121
20131
20148
20157
20164
20176
20189
20199
20202
20218
202215
20238
202418
202513
202649

How FDAgent sorts observations into this theme

Two fixed rules, applied by code to every observation FDAgent can quote. An observation counts when either holds. No model and no similarity score decides.

It is tied to one of these 21 CFR entries

21 CFR 211.4221 CFR 211.4421 CFR 211.4621 CFR 211.4821 CFR 211.5021 CFR 211.5221 CFR 211.58

A 483 prints no regulation, so FDAgent ties an observation to a section only when it opens with FDA's own citation wording for that section, word for word.

Or its text contains one of these phrases

“HVAC” · “air handl*” · “AHU*” · “pressure differential*” · “differential pressure*” · “temperature and humidity” · “humidity control*” · “humidity monitor*” · “air change*” · “air filtration” · “state of repair” · “ceiling tile*” · “peeling” · “flaking” · “water leak*”

* matches any ending and … up to three words in between. Case is ignored unless a phrase has capitals.

The 160 observations, newest first

Quoted word for word from each Form 483, with only line breaks joined; … marks where the quote is cut. The highlight shows why the observation is in this theme. Each links to FDAgent's page for the 483.

  1. Front Door Pharmacy, LLC dba Pure PharmacyInspection ended Mar 18, 2019 · FEI 3012937475 · Observation 8

    Laboratory test equipment used in the preparation and testing of collected samples are inadequate. Specifically, your firm uses a [redacted model] for the incubation of collected media-fills. The unit fails to have adequate temperature and related humidity controls to perform and control these environmental conditions.

    Contains “humidity control*”Read the Form 483 →

  2. Intrathecal Compounding Specialist, LLCInspection ended Feb 14, 2019 · FEI 3006372310 · Observation 2

    Inadequate pressure differentials between higher quality air room and lower quality air rooms were observed. Specifically, you had negative or zero pressure for short periods of time in the buffer room (ISO 7) and anteroom (ISO 8) on January 2, 2019. Additionally, there were multiple times on twenty-one days when the pressure was lost in the [(b) (4)] room from November 28, 2018 to December 28, 2018. You have no pressure data for January 24, 2019 …

    Contains “pressure differential*”Read the Form 483 →

  3. Inventive Infusion Solutions, LPInspection ended Aug 31, 2018 · FEI 3014498447 · Observation 7

    Unsealed, loose ceiling tiles were observed in your cleanroom. Specifically, On 08/24/2018, I observed visible gaps of approximately 0.5 cm between the HEPA filter grate panel and the ceiling panel frame and between the ceiling panel and the wall panel inside the ISO 7 clean room. These gaps are above the ISO 5 (b)(4) hood that is being used for aseptic processing/sterilization processes. The ISO 5 (b)(4) hood was observed being used by operator …

    Contains “ceiling tile*”Read the Form 483 →

  4. The Pet Apothecary LLCInspection ended Aug 7, 2018 · FEI 3005946041 · Observation 1

    … 50mg/mL on 7/13/2018 Additionally, there are no controls or procedures in place for production of beta-lactam drugs to be contained within a separate air handling unit. The use of (b) (4) HEPA-filtered containment hoods for production of beta-lactam drugs is optional, as reported by the pharmacist-in-charge.

    Contains “air handl*”Read the Form 483 →

  5. Auro PharmaciesInspection ended Aug 2, 2018 · FEI 3011893599 · Observation 10

    OBSERVATION 10 Buildings used in the manufacture, processing, packing, or holding of a drug product do not have the suitable construction to facilitate cleaning, maintenance, and proper operations. Specifically, A. On 07/09/2018, we observed a gap, approximately 1/4 inch by 1/2 inch, under the south door that opens to a hallway leading to the unclassified pre-gown room. B. On 07/18/2018, in the ISO 8 classified prep room, we observed a lack of …

    Opens with FDA's citation wording for 21 CFR 211.42(a)Read the Form 483 →

  6. Biotika ASInspection ended Jun 1, 2018 · FEI 3003370212 · Observation 1

    … Differential pressure of the personnel (b) (4), material (b) (4), and (b) (4) area. ii. Relative humidity and temperature of the (b) (4) area. C. Volume of water used to [illegible] and of solution of (b) (4) in storage tank 78301 are not documented in the batch production records for (b) (4).

    Contains “differential pressure*”Read the Form 483 →

  7. Ranier’s Compounding LaboratoryInspection ended May 22, 2018 · FEI 3012124170 · Observation 8

    Procedures designed to identify and prevent insanitary conditions are not established and followed by your firm. Specifically, 1. Your firm did not ensure appropriate certification of your aseptic processing areas. For example, a. During certification of your aseptic processing area on 02/12/18, testing showed pressure differential failure between the gowning room and the unclassified general pharmacy. This failure was not corrected until …

    Contains “pressure differential*”Read the Form 483 →

  8. Eagle Pharmacy Inc.Inspection ended May 18, 2018 · FEI 3011688532 · Observation 3

    Aseptic processing areas are deficient regarding systems for the aseptic conditions. Specifically, there is [illegible] used to monitor pressure differentials, temperature, and relative [illegible] classified areas used for sterile compounding.

    Contains “pressure differential*”Read the Form 483 →

  9. One Way Drug LLC dba Partell Specialty PharmacyInspection ended Mar 8, 2018 · FEI 3011769075 · Observation 9

    Inadequate pressure differentials between higher quality air rooms and lower quality air rooms were observed. Specifically, a. Sterile drug filling is conducted inside the ISO 5 core of Laminar Air Flow Hood (LAFH). The evaluation of unidirectional airflow (e.g., smoke studies) for microbiological contamination was not performed under dynamic conditions in the ISO 5 LAFH, which is located in an ISO 7 environment. b. During filling operations, we …

    Contains “pressure differential*”Read the Form 483 →

  10. Aurobindo Pharma Ltd.Inspection ended Feb 20, 2018 · FEI 3008461619 · Observation 1

    Aseptic processing areas are deficient regarding systems for maintaining any equipment used to control the aseptic conditions. Specifically, on February 13, 2018 during the machine set-up and filling preparation for ®® | injection lot # ®®, I observed dirty ®® | with black stains on the filling machine and mentioned it to the management. No action was taken by the management on that day. On Feb. 14, 2018, I observed that the filling is in process …

    Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(vi)Read the Form 483 →

  11. Option Care Enterprises Inc. dba Option CareInspection ended Feb 8, 2018 · FEI 3012188090 · Observation 3

    … The firm is not monitoring differential pressures from the buffer room to this space. The firm does not include this uncontrolled refrigerated pass through in its environmental monitoring.

    Contains “differential pressure*”Read the Form 483 →

  12. I.V. Specialty Ltd.Inspection ended Jul 28, 2017 · FEI 3010836489 · Observation 2

    … The ceiling of the ISO 7 clean room has a tear in the plastic surface of the drop-ceiling tile approximately 13 feet from the LAF Hood used for processing sterile drugs. This tear exposes the dry-wall material behind the plastic layer. Note: Items C, D, E, F, and G are repeat observations from the Inspection in February 2016

    Contains “ceiling tile*”Read the Form 483 →

  13. Triad Isotopes Inc.Inspection ended Jul 3, 2017 · FEI 3008364285 · Observation 5

    Your firm does not measure the pressure differential between the ISO 5 hood used for sterile operations and the surrounding area.

    Contains “pressure differential*”Read the Form 483 →

  14. ARJ Infusion Services, Inc.Inspection ended May 25, 2017 · FEI 3013452490 · Observation 1

    Aseptic processing areas are deficient regarding the system for monitoring environmental conditions. Specifically, A. You have not performed your media fill during worst case processing conditions of your sterile processed drugs. B. Your main pharmacy technician has not performed a media fill at your current address. C. You have not performed dynamic smoke studies in your laminar air flow hood. D. Air pressures are not monitored during sterile …

    Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(iv)Read the Form 483 →

  15. ARJ Infusion Services, Inc.Inspection ended May 25, 2017 · FEI 3013452490 · Observation 3

    Aseptic processing areas are deficient regarding the system for cleaning and disinfecting the room and equipment to produce aseptic conditions. Specifically, I observed sterile processing of Normal Saline/Sodium Chloride 0.9% (identified by raw material lot (b) (4) and (b) (4)) conducted by your Pharmacy Technician in your laminar air flow hood on 5/16/2017 and 5/17/2017. During sterile processing, I observed the following inadequate aseptic …

    Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(v)Read the Form 483 →

  16. Park Infusioncare LP dba Preferred HomecareInspection ended Feb 17, 2017 · FEI 3012669716 · Observation 1

    … The ISO 7 anteroom has a ceiling made of ceiling tiles like found in an office space. Gaps were observed around ceiling tile and the HEPA filter in the ceiling of the ISO 7 anteroom such that there was a continuous space between the ISO 7 anteroom and the unclassified area above the ceiling. Additionally, the HEPA filter appeared distorted at the edge of the filter. g. The sink in the ISO 7 anteroom has a work surface made of wood covered either …

    Contains “ceiling tile*”Read the Form 483 →

  17. Bayer AG PharmaInspection ended Jan 20, 2017 · FEI 3002806462 · Observation 6

    Failure to establish separate areas to prevent cross contamination. There is no process to analytically measure pressure differentials between production rooms and common corridors in the non-product dedicated (b) (4) production plant. (b) (4) are used to indicate the air flow between areas, but operators are not always present to ensure the proper flow of air during production activities. On 19 January 2017, the (b) (4) between the (b) (4) room …

    Contains “pressure differential*”Read the Form 483 →

  18. Montana Compounding Pharmacy P.C.Inspection ended Sep 20, 2016 · FEI 3011412185 · Observation 3

    OBSERVATION 3 Non-microbial contamination was observed in your production area. Specifically, One section of the dust covered louver blades of the HVAC system was missing over the production area. Uncontrolled airflow from this missing louver section would allow for undesired particulates into uncovered, weighed [(b)(4)] active pharmaceutical ingredients and components for production.

    Contains “HVAC”Read the Form 483 →

  19. Qingdao Kangyuan Pharmaceutical Co., LTDInspection ended Apr 22, 2016 · FEI 3006512854 · Observation 3

    During our walkthrough of the Building (b)(4) which is used for (b)(4) API production, your firm explained that the HVAC, ID #SC-KTJ-12-01, for clean rooms class D is powered off during non-operation. It was further explained that the HVAC power is turned on for (b)(4) during non-operation. Since the HVAC system is re-qualified (b)(4) and was last re-qualified on 7/12/2015, no data was presented as to its qualification status when the system is …

    Contains “HVAC”Read the Form 483 →

  20. Drug Depot Inc. dba APS PharmacyInspection ended Jan 22, 2016 · FEI 3010621916 · Observation 3

    Aseptic processing areas are deficient regarding the system for monitoring environmental conditions. Specifically, A. Air (viable and non-viable) sampling within all classified areas is not performed during daily [illegible]. Personnel stated that sampling is only performed every [illegible]. B. There is no continuous or at least periodically monitoring of air pressure differentials during production from the ISO 7 room containing the ISO 5 hoods …

    Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(iv)Read the Form 483 →

21 CFR sections these observations open with

The sections FDAgent ties the most of these observations to by FDA's wording, with how many of this theme's observations each covers. Each links to its page of FDA citations, warning letters and the regulation text.

Ask FDAgent about facilities and HVAC in Form 483s

FDAgent reads FDA's Form 483s, inspections, citations and warning letters and answers in plain English, with links to the records.

Edit it or ask as written. 3 questions free, no card needed.

About this data

  • The observations are the text FDAgent read by OCR from Form 483 PDFs in FDA's Electronic Reading Room, shown only from 483s whose every printed observation passed FDAgent's checks against the scanned text, as on each 483's own page.
  • Which theme an observation belongs to is decided by the fixed rules above; every count on this page is computed from them.
  • A 483 addressed to an individual is listed without the name, and an observation that names a person is left out.
  • FDAgent is independent of FDA.