Buildings, facilities and HVAC in FDA Form 483 observations
The plant itself: building design and repair, air handling, pressure differentials, temperature and humidity. FDAgent finds 160 such observations in 121 Form 483s issued to 117 facilities, for inspections that ended between October 2008 and September 2026. Each is quoted below from the 483 FDA posted.
A Form 483 lists the investigators' observations at the end of an inspection. It is not FDA's final determination.
Source: Form 483 PDFs in FDA's Electronic Reading Room, last synced Nov 23, 2026, 04:33 UTC. Every quote is from a 483 whose reading passed FDAgent's checks against the scan. FDAgent is independent of FDA.
- Observations
- 160
- Each quoted below
- Form 483s
- 121
- Posted by FDA
- Facilities
- 117
- Distinct FEIs
- Most recent
- Sep 10, 2026
- Inspection end date
Observations by year
These observations by the year the inspection ended. They follow which 483s FDA has posted and FDAgent has read, so they show what is on record, not a trend in FDA's findings. 2026 runs to the latest sync (lighter bar).
Peak: 49 in 2026
| Year | Observations |
|---|---|
| 2008 | 1 |
| 2009 | 1 |
| 2010 | 0 |
| 2011 | 0 |
| 2012 | 1 |
| 2013 | 1 |
| 2014 | 8 |
| 2015 | 7 |
| 2016 | 4 |
| 2017 | 6 |
| 2018 | 9 |
| 2019 | 9 |
| 2020 | 2 |
| 2021 | 8 |
| 2022 | 15 |
| 2023 | 8 |
| 2024 | 18 |
| 2025 | 13 |
| 2026 | 49 |
How FDAgent sorts observations into this theme
Two fixed rules, applied by code to every observation FDAgent can quote. An observation counts when either holds. No model and no similarity score decides.
It is tied to one of these 21 CFR entries
21 CFR 211.4221 CFR 211.4421 CFR 211.4621 CFR 211.4821 CFR 211.5021 CFR 211.5221 CFR 211.58
A 483 prints no regulation, so FDAgent ties an observation to a section only when it opens with FDA's own citation wording for that section, word for word.
Or its text contains one of these phrases
“HVAC” · “air handl*” · “AHU*” · “pressure differential*” · “differential pressure*” · “temperature and humidity” · “humidity control*” · “humidity monitor*” · “air change*” · “air filtration” · “state of repair” · “ceiling tile*” · “peeling” · “flaking” · “water leak*”
* matches any ending and … up to three words in between. Case is ignored unless a phrase has capitals.
The 160 observations, newest first
Quoted word for word from each Form 483, with only line breaks joined; … marks where the quote is cut. The highlight shows why the observation is in this theme. Each links to FDAgent's page for the 483.
GE HealthCareInspection ended Feb 7, 2025 · FEI 3002807778 · Observation 2
… Additionally, the air filtration system within the blower unit does not adequately capture drug particles from the filling operations and the drug particles are exhausted inside the common production area. The blower/filtration unit was observed with coating of (b) (4) particles, resembling drug substances, and visible (b) (4) particles were observed in the surrounding manufacturing area. The blower unit is equipped with general particle filter …
Contains “air filtration”Read the Form 483 →
Zhejiang Huahai Pharmaceutical Co., Ltd.Inspection ended Jan 24, 2025 · FEI 3003999190 · Observation 5
OBSERVATION #5 Aseptic processing areas are deficient regarding systems for maintaining any equipment used to control the aseptic conditions. On 16-Jan-2025, a 2 x 126 cm piece of non-sterile tape was observed between I (bTC4J t5haring 41 (b)( These sit below the HEPA filters and above where empty vials enter the line from the (b)(4} 4 I (b)(~ before being aseptically filled within Workshop~ the tape was placed between these (b)(~ seal an …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(vi)Read the Form 483 →
Janssen Vaccines CorporationInspection ended Nov 19, 2024 · FEI 3012637764 · Observation 3
Aseptic processing areas are deficient regarding systems for maintaining any equipment used to control the aseptic conditions. Specifically, A. Aseptic filling processing of finished drug product i.e. from (b) (4) vials to aseptic filling and to glass vial sealing processing steps, are performed within a Grade A (ISO 5) environment. The following observation was made regarding your non-viable particle (NVP) monitoring: You manufacture (b) (4) …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(vi)Read the Form 483 →
Janssen Vaccines CorporationInspection ended Nov 19, 2024 · FEI 3012637764 · Observation 4
Aseptic processing areas are deficient regarding the system for cleaning and disinfecting the room and equipment to produce aseptic conditions. Specifically, Your (b) (4) stoper transfer pipe was seen to have a small hook (~1.5 cm) like structure welded on the top of the pipe. The welding was rough and consisted of a crack at the welding site. On the inside of the pipe right beneath the welded hook, the surface was not smooth, appeared to be (b) …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(v)Read the Form 483 →
Staska Pharmaceuticals IncInspection ended Sep 18, 2024 · FEI 3017473850 · Observation 4
Aseptic processing areas are deficient regarding the system for monitoring environmental conditions. Specifically, According to SOP MC010, Environmental Monitoring, Rev 06, microbial contamination recovery limits for the elbows or gowning elements of operators are set at Alert: NA and Action: (b) (4), while the limit for hands or gloves entering the Grade A area is Action (b) (4) However, when operators conduct interventions in which they open …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(iv)Read the Form 483 →
Staska Pharmaceuticals IncInspection ended Sep 18, 2024 · FEI 3017473850 · Observation 5
Aseptic processing areas are deficient regarding the system for cleaning and disinfecting the room and equipment to produce aseptic conditions. Specifically, A. Your firm has not conducted a cleaning validation on product contact equipment including stainless steel mixing pots and mixing impellers to assure your cleaning process removes microbial content or chemical residues on the equipment used in your aseptic operations. (b) (4) stainless …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(v)Read the Form 483 →
Rechon Life Science ABInspection ended Sep 6, 2024 · FEI 3002806978 · Observation 1
Separate or defined areas to prevent contamination or mix-ups are deficient regarding operations related to aseptic processing of drug products. There is no assurance that the current flow of personnel through the different rooms in the aseptic area in Building (b) (4) is designed to prevent microbial contamination in the aseptic core. Your current procedures require personnel to leave the aseptic processing room and its critical areas and travel …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)Read the Form 483 →
Rechon Life Science ABInspection ended Sep 6, 2024 · FEI 3002806978 · Observation 2
… This does not provide assurance that the Grade A conditions, including flow laminarity and air changes are continuously kept during commercial aseptic filling. 2. Inadequate aseptic behavior during set-up process for commercial filling of (b) (4) mcg/mL, lot (b) (4) on Line (b) (4) Ampoule line). Specifically, A. We observed at the end of the assembly process the manufacturing operator touching the (b) (4) of the (b) (4) (b) (4) with the palm of …
Contains “air change*”Read the Form 483 →
Rechon Life Science ABInspection ended Sep 6, 2024 · FEI 3002806978 · Observation 3
Aseptic processing areas are deficient regarding the system for cleaning and disinfecting the equipment to produce aseptic conditions. Your procedure SOP 2181 version 2.0, Effective date: 2023-11-09 (b) (4) Dekontaminering av lokaler på Bulk Production (b) (4) Sanitization - Decontamination of rooms at Bulk Production" for the (b) (4) decontamination and sanitization of Grade A and Grade B production areas using (b) (4) (b) (4) is inadequate. …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(v)Read the Form 483 →
Rechon Life Science ABInspection ended Sep 6, 2024 · FEI 3002806978 · Observation 4
Aseptic processing areas are deficient regarding the system for monitoring environmental conditions. Risk Assessment Report QGL-1015-02 titled "Identification of critical monitoring locations for viable and non-viable particles on the ampoule filling line", approved on 04/02/2024, justifies the environmental monitoring locations of ampoule filling line. On 08/26/2024, during our assessment of the filling line assembly operations for the …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(iv)Read the Form 483 →
Rechon Life Science ABInspection ended Sep 6, 2024 · FEI 3002806978 · Observation 6
Your firm failed to maintain buildings used in the manufacture, processing, packing or holding of drug products in a good state of repair. During the walking tour of your aseptic processing areas, the walls of the production Rooms (b) (4) and (b) (4) and the floor of the Room (b) (4) in the Grade D aseptic areas were observed to be sticky to the touch. This condition suggested inadequate cleaning and maintenance practices within the controlled …
Contains “state of repair”Read the Form 483 →
Huangshi Hygenic Material Medicine Co.Inspection ended Aug 30, 2024 · FEI 3005543486 · Observation 7
Buildings used in the manufacturing and processing of a drug product are not maintained in a good state of repair. Specifically, The building used in the processing and storing of the raw materials was not maintained in a good state of repair including A) The ceiling of raw material storage room had water damage stains and peeling paint above the bags storing raw ingredients. B) A door of the ingredient (API, (b) (4)) room was damaged and had …
Opens with FDA's citation wording for 21 CFR 211.58Read the Form 483 →
Qingdao Kangyuan Pharmaceutical Co., LTDInspection ended Aug 16, 2024 · FEI 3006512854 · Observation 4
Equipment used in the manufacture of intermediates and API's should be maintained in a good state of repair to prevent contamination that would alter the safety, identity, strength, quality and purity of the drug product. Specifically, During the inspectional walkthrough, on 08/12/2024 it was observed that your firm failed to maintain equipment used in the manufacturing of API and intermediates in a good state of repair. Your (b)(4) located …
Contains “state of repair”Read the Form 483 →
Nubratori, IncInspection ended Jul 26, 2024 · FEI 3010166491 · Observation 2
Aseptic processing areas are deficient regarding the system for monitoring environmental conditions. Specifically, On 07/17/2024, during the production of Lidocaine HCl/Tetracaine HCl (Lot#[(6 ) I observed that the technician collect their glove fingertip personnel monitoring samples, after wiping a piece sampling equipment with Sterile[(b) (4)], and samples were not taken immediately after completion of aseptic operations. Personnel monitoring …
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(iv)Read the Form 483 →
Nubratori, IncInspection ended Jul 26, 2024 · FEI 3010166491 · Observation 3
Aseptic processing areas are deficient regarding the system for cleaning and disinfecting the room and equipment to produce aseptic conditions. Specifically, On 07/17/2024, during the production of Lidocaine HCl/Tetracaine HCl (Lot#[(b) (4)] I observed that the operator failed to wipe down the ISO 7 side [(6) (4)] before opening it to receive materials and failed to clean the legs of the ISO 5 [(6) (4)] air flow hood before aseptic operations.
Opens with FDA's citation wording for 21 CFR 211.42(c)(10)(v)Read the Form 483 →
Taenaka Kogyo Co., Ltd.Inspection ended Apr 12, 2024 · FEI 3003282619 · Observation 2
… a) The heating, ventilation, and air conditioning (HVAC) system used to establish the specified differential pressure between the production suites and the neighboring outside environment are not sufficient to ensure this pressure differential is maintained. On 04/09/24, I observed the gauge displaying the pressure differential between the Plant [illegible] room and the outside environment drop to less than [illegible], which is below the …
Contains “HVAC”Read the Form 483 →
Taenaka Kogyo Co., Ltd.Inspection ended Apr 12, 2024 · FEI 3003282619 · Observation 3
Facilities for the storage of materials under controlled temperature and humidity conditions are not sufficiently monitored to ensure the material characteristics of items stored inside them are maintained. Specifically, The controlled temperature storage chambers used by your firm to store various materials involved in GMP drug substance manufacturing operations are not monitored in a way that ensures temperature excursions are addressed in a …
Contains “temperature and humidity”Read the Form 483 →
MSN Laboratories Private Limited, Unit-IIInspection ended Mar 22, 2024 · FEI 3008656542 · Observation 1
Your firm failed to properly maintain buildings and facilities used in the manufacture of API in a clean condition. Specifically, during a walkthrough of your facility on March 18, 2024, I observed what appeared to be water staining and unknown residue on ceiling tiles located above retain samples, as well as on the baseboard behind the retains, in your API Reserve Sample Storage Room. Examples of retain samples stored in the API Reserve Sample …
Contains “ceiling tile*”Read the Form 483 →
Jiangsu Hengrui Pharmceuticals Co., LtdInspection ended Jan 16, 2024 · FEI 3007373503 · Observation 7
Buildings used in the holding of a drug product are not maintained in a good state of repair. Specifically, During our walkthrough of your warehouse facility refrigerator (2 - 8°C) on 01/12/2024, we observed what appeared to be a pool of water (approximately 100 square feet) on the floor of the warehouse with pallets of released finished parenteral drug products stored directly over this water. In addition, we observed a second pool of water near …
Opens with FDA's citation wording for 21 CFR 211.58Read the Form 483 →
Jiangsu Hengrui Pharmceuticals Co., LtdInspection ended Jan 16, 2024 · FEI 3007373503 · Observation 8
Washing and toilet facilities lack hot and cold water. Specifically, During the inspection of your (b)(4) parenteral drug product workshop (b)(4) we observed that is no hot/warm water in the washing facility prior to the entrance of the Clothes Sterilization room Grade D on 01/11/2024. Additionally, our workshop manager confirmed that there is no warm/hot water at any of the hand washing stations for the entire workshop, including the washing …
Opens with FDA's citation wording for 21 CFR 211.52Read the Form 483 →
21 CFR sections these observations open with
The sections FDAgent ties the most of these observations to by FDA's wording, with how many of this theme's observations each covers. Each links to its page of FDA citations, warning letters and the regulation text.
- 21 CFR 211.42Design and construction featuresIn this theme's rule60
- 21 CFR 211.58MaintenanceIn this theme's rule8
- 21 CFR 211.22Responsibilities of quality control unit4
- 21 CFR 211.113Control of microbiological contamination4
- 21 CFR 211.192Production record review4
- 21 CFR 211.44LightingIn this theme's rule1
- 21 CFR 211.52Washing and toilet facilitiesIn this theme's rule1
- 21 CFR 211.56Sanitation1
- 21 CFR 211.63Equipment design, size, and location1
- 21 CFR 211.68Automatic, mechanical, and electronic equipment1
Ask FDAgent about facilities and HVAC in Form 483s
FDAgent reads FDA's Form 483s, inspections, citations and warning letters and answers in plain English, with links to the records.
Related
About this data
- The observations are the text FDAgent read by OCR from Form 483 PDFs in FDA's Electronic Reading Room, shown only from 483s whose every printed observation passed FDAgent's checks against the scanned text, as on each 483's own page.
- Which theme an observation belongs to is decided by the fixed rules above; every count on this page is computed from them.
- A 483 addressed to an individual is listed without the name, and an observation that names a person is left out.
- FDAgent is independent of FDA.