Skip to content

MANCHESTER VA MEDICAL CENTER

718 Smyth Rd, Manchester, New Hampshire, United States

FEI 3012708598

FDA has one inspection on file for MANCHESTER VA MEDICAL CENTER in Manchester, New Hampshire (FEI 3012708598). It ended on and was classified VAI, voluntary action indicated.

VAI means FDA investigators found objectionable conditions or practices, but FDA was not prepared to take or recommend regulatory action. The firm is expected to correct them voluntarily.

FDA published 8 citations from this inspection. They are listed below. One FOIA request has asked FDA for this inspection's 483.

No warning letter, court action or import refusal is filed under this FEI.

Sources:FDA firm profile ↗Synced Nov 23, 2026

Ask FDAgent about this site

Free account: 3 questions, no card needed. Each answer links to its FDA sources.

Email me when FDA posts a new inspection, Form 483 or warning letter for this site

Weekly, on a free account. Pause it any time.

Watch this facility

Comparing suppliers? Check this site beside 2 others, free

Latest inspection
VAI
Inspections on file
1, in 2020
Inspections with 483 observations shown
1 of 1
Form 483s posted by FDA
None held for this FEI
Requested under FOIA
1 request, latest Nov 18, 2025
Warning letters
None on file
Import refusals
None under this FEI
Import alerts
Not linked by FEI
FDA lists import alert firms by name and address, rarely by FEI. Check FDA’s import alert list ↗

Inspection history

1 inspection · FDA Data Dashboard, last synced Nov 23, 2026, 04:25 UTC

  1. VAIObjectionable conditions found; FDA took no regulatory actionDrugs · Drug Quality Assurance8 citations published

    FDA’s citation titles and text from its Data Dashboard. These are FDA’s summaries, not the Form 483 itself.

    1. FDCA 501(a)(2)(A)

      Inadequate HEPA filter, sterile product area

      You had inadequate HEPA filter coverage and airflow over the area to which sterile product was exposed.

    2. FDCA 501(a)(2)(A)

      Disinfecting and cleaning agents, ISO 5 area

      Disinfecting agents and cleaning pads and cleaning wipes used in the ISO 5 classified aseptic processing areas were not sterile.

    3. FDCA 501(a)(2)(A)

      Non-microbial contamination, production area

      Non-microbial contamination was observed in your production area.

    4. FDCA 501(a)(2)(A)

      Inadequate control, construction adjacent to drug production

      Your firm produced drugs while construction was underway in an adjacent area without adequate controls to prevent contamination of the production environment and product.

    5. FDCA 501(a)(2)(A)

      Air flow quality, higher classified area

      Your facility design allowed the influx of poor quality air into a higher classified area.

    Show 3 more citations
    1. FDCA 501(a)(2)(A)

      Actionable microbial contamination, adjacent area

      You did not make adequate product evaluation and take remedial action where actionable microbial contamination was found to be present in an area adjacent to the ISO 5 classified aseptic processing area during aseptic production.

    2. FDCA 501(a)(2)(A)

      Ceiling tiles, cleanroom

      Unsealed, loose ceiling tiles were observed in your cleanroom.

    3. FDCA 501(a)(2)(A)

      Dust-collecting overhangs, surrounding area of ISO 5

      The segregated production areas surrounding the ISO 5 classified aseptic processing area contained dust-collecting overhangs without adequate and frequent cleaning.

Requested under FOIA

FDA FOIA logs, last synced Nov 23, 2026, 04:25 UTC

One request to FDA under the Freedom of Information Act named this site, on Nov 18, 2025. It asked for a Form 483.

  • Inspection ending Jan 27, 2020VAI

    1 request. In the inspection history above. FDA released records in answer to a request for its Form 483 on Jan 22, 2026. FDAgent holds no copy that FDA posted.

    1. Nov 18, 2025FDA-FOIA-2025-13117Form 483· 1 of 5 sitesRecords released

A request is listed when it names this site’s FEI number or one of its FDA inspection IDs, or, after review, its exact street address. Requester names are left out.

Go further than this page

FDAgent researches FDA’s records and links every answer to its source.

Free account: 3 questions, no card needed.

About this data. Every record here is filed under FEI 3012708598 in FDA’s data. FDAgent is independent of FDA, and FDA’s firm profile is the authoritative record.
  • Every record on this page is filed under FEI 3012708598. Records filed under another FEI or name, including other sites of the same company, are not shown here.
  • FDA posts only some Form 483s. A missing 483 does not mean no observations were issued, and classifications can change after FDA review.
  • Recalls are not shown, because FDAgent does not hold them by FEI. Import alerts are shown when FDA printed this FEI beside the firm on the alert, or when a Red List entry’s firm name, street address and country equal an inspection record under this FEI and no other FEI has that name. FDA lists most firms by name and address alone, so a site can be on an import alert without it appearing here.
  • “Last synced” is when FDAgent last copied that FDA source. FDA often publishes a record weeks after the inspection or action it describes.
  • Observation text comes from OCR of the scanned PDF. FDAgent keeps an observation only when it matches the scanned text, and marks unreadable spans [illegible]. Last synced Nov 23, 2026, 04:30 UTC.
  • FDAgent is independent and not affiliated with FDA. Check the FDA firm profile for the authoritative record.